Set point programmer

Devices supported

The following table lists the devices that support the set point Also known as SP. The desired value of a process variable. Setpoint (SP) is an analog point parameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. programmer, and their formats.

Device Supported Address Format Range

DR4300

SPP Setpoint in percent. See also: setpoint parameter. [n] [param]

[n] = 1 to 1

DR4500

SPP [n] [param]

[n] = 1 to 2

UDC2300

SPP [n] [param]

[n] = 1 to 1

UDC3300

SPP [n] [param]

[n] = 1 to 1

UMC800

SPP [n] [param]

[n] = 1 to 4

HC900 Hybrid controller.

SPP [n] [param]

[n] = 1 to 4

Parameters

The following table lists the details of the set point program parameters.

Param Address Line Param Format Access Devices

Set Point Programmer Output

SPP [n] OUT1

Floating Point

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Segment Time Remaining

SPP [n] SEG_TIME_REM

Floating Point

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Start

SPP [n] START

UINT2

WO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Hold

SPP [n] HOLD

UINT2

WO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Advance

SPP [n] ADV

UINT2

WO

UMC800, HC900

Set Point Programmer Reset

SPP [n] RESET

UINT2

WO

UMC800, HC900

Set Point Programmer Status - Ready

SPP [n] STATUS_READY

Discrete (bits).

[Status Point A type of standard point that is used to represent discrete or digital field values. See also: dual-bit status point, standard point. Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Run

SPP [n] STATUS_RUN

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Hold

SPP [n] STATUS_HOLD

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - End

SPP [n] STATUS_END

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Time Units in Seconds

SPP [n] STATUS_TIME_UNIT In the Experion Batch Manager context, a collection of associated control modules and/or equipment modules and other process equipment in which one or more major processing activities can be conducted. - This term applies to both the physical equipment and the equipment control. - Examples of major processing activities are react, crystallize, and make a solution._S

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Time Units in Minutes

SPP [n] STATUS_TIME_UNIT_M

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Time Units in Hours

SPP [n] STATUS_TIME_UNIT_H

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Elapsed Time

SPP [n] EL_TIME

Floating Point

RO

UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Status - Ramp Rate

SPP [n] STATUS_RAMP_RATE

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300

Set Point Programmer Status - Ramp Units

SPP [n] STATUS_RAMP_UNITS

Discrete (bits).

[Status Point Only]

RO

DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900

Set Point Programmer Current Segment Number

SPP [n] SEG_NO

Floating Point

RO

DR4300, DR4500, UDC2300, UDC3300

Set Point Programmer Current Segment Number

SPP [n] SEG_NO

Floating Point

RW

UMC800, HC900

Set Point Programmer Status - Type of Hold

SPP [n] STATUS_HOLD_TYPE

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Status - Current Segment is a ramp

SPP [n] STATUS_RAMP

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #1

SPP [n] EV01

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #2

SPP [n] EV02

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #3

SPP [n] EV03

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #4

SPP [n] EV04

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #5

SPP [n] EV05

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #6

SPP [n] EV06

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #7

SPP [n] EV07

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #8

SPP [n] EV08

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #9

SPP [n] EV09

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #10

SPP [n] EV10

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #11

SPP [n] EV11

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #12

SPP [n] EV12

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #13

SPP [n] EV13

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #14

SPP [n] EV14

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #15

SPP [n] EV15

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Set Point Programmer Segment Event #16

SPP [n] EV16

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900