About configuring history backfill
After you have assigned points to the Trend Point function block A unit of data and operation within Experion. Experion uses blocks as the component from which control strategies are built. The two categories of blocks are hardware entities and functional entities. in the controller, these points must also be assigned to standard history The type of history that collects one-minute snapshots of point parameter values, as well as a number of averages based on those one-minute snapshots. Compare: exception history, extended history, fast history. See also: history, point parameter. on the server The computer on which the Experion database software and server utilities run. See also: Experion server TPS.. This can be done using Quick Builder The Experion tool used to configure system components, such as standard points, Flex Stations, controllers (other than process controllers), electronic flow measurement (EFM), and printers. See also: controller, electronic flow measurement (EFM), Flex Station, process controller, standard point. (recommended) or directly in Station Experion's main operator interface. Station presents information using a series of displays. See also: display. via the History Assignment displays. You can optionally configure History Archiving (see the topic "History Archiving" in the
Configuring history backfill
To allow the history backfill process to operate, you need to change some server settings. Use Station to make these changes.
ATTENTION: Selecting to enable history backfill using the steps below does not trigger a backfill of history; it only enables the history backfill option.
To trigger a backfill of history for a particular controller, go to that controller’s status display and clear the Enable History Backfill check box for at least one minute. Then, select the Enable History Backfill check box. This will trigger history backfill for that controller.
In HC (Hybrid Control) Designer, when configuring Trend Backfill Log Point Selection, you must select Use Modbus Address.
To configure history backfill:
-
From the Station menu, choose ConfigureSystem HardwareServer Wide Settings.
-
Select the History Backfill tab.
-
Select the Enable history backfill check box to enable history backfill.
-
In the Maximum number of days to backfill box, enter the maximum number of days that history can be backfilled (23 recommended).
Any event data older than this number of days will be discarded and will not be inserted into history. This maximum number of days must not exceed the number of days of standard history snapshots that is configured for the system.