Set point scheduler values
Devices supported
The following table lists the devices that support the Set Point Also known as SP. The desired value of a process variable. Setpoint (SP) is an analog point parameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. Scheduler A facility used to schedule the control of a point on either a periodic or once only (demand) basis. See also: demand scan, periodic scan, point. Values, and their formats.
| Device | Supported Address Format | Range |
|---|---|---|
|
UMC800 |
SCHED [n] [param] |
[n] = 1 to 1 |
|
SCHED [n] [param] |
[n] = 1 to 2 |
Parameters
The following table lists the details of the Scheduler Values parameters.
| Param | Address Line | Param Format | Access | Devices |
|---|---|---|---|---|
|
Output #1 |
SCHED [n] OUTPUT11 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #1 |
SCHED [n] OUTPUT2 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #1 |
SCHED [n] OUTPUT3 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #4 |
SCHED [n] OUTPUT4 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #5 |
SCHED [n] OUTPUT5 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #6 |
SCHED [n] OUTPUT6 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #7 |
SCHED [n] OUTPUT7 |
Floating Point |
RO |
UMC800, HC900 |
|
Output #8 |
SCHED [n] OUTPUT8 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #1 |
SCHED [n] AUX_OUT1 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #2 |
SCHED [n] AUX_OUT2 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #3 |
SCHED [n] AUX_OUT3 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #4 |
SCHED [n] AUX_OUT4 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #5 |
SCHED [n] AUX_OUT5 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #6 |
SCHED [n] AUX_OUT6 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #7 |
SCHED [n] AUX_OUT7 |
Floating Point |
RO |
UMC800, HC900 |
|
Auxiliary Output #8 |
SCHED [n] AUX_OUT8 |
Floating Point |
RO |
UMC800, HC900 |
|
Current Program Number |
SCHED [n] PROG_NO |
Floating Point |
RW |
UMC800, HC900 |
|
Current Segment Number |
SCHED [n] SEG_NO |
Floating Point |
RW |
UMC800, HC900 |
|
Program Elapsed Time |
SCHED [n] EL_TIME |
Floating Point |
RO |
UMC800, HC900 |
|
Segment Time Remaining |
SCHED [n] TIME_REMAIN |
Floating Point |
RO |
UMC800, HC900 |
|
Schedule Save Request |
SCHED [n] SCHED_SAVE |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #1 |
SCHED [n] SOAK_LIMIT_1 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #2 |
SCHED [n] SOAK_LIMIT_2 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #3 |
SCHED [n] SOAK_LIMIT_3 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #4 |
SCHED [n] SOAK_LIMIT_4 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #5 |
SCHED [n] SOAK_LIMIT_5 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #6 |
SCHED [n] SOAK_LIMIT_6 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #7 |
SCHED [n] SOAK_LIMIT_7 |
Floating Point |
RW |
UMC800, HC900 |
|
Guaranteed Soak Limit #8 |
SCHED [n] SOAK_LIMIT_8 |
Floating Point |
RW |
UMC800, HC900 |
|
Jog Segment |
SCHED [n] JOG_SEG |
Floating Point |
RW |
UMC800, HC900 |
|
Event #1 |
SCHED [n] EVENT_01 |
Discrete (bits). |
RO |
UMC800, HC900 |
|
Event #2 |
SCHED [n] EVENT_02 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #3 |
SCHED [n] EVENT_03 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #4 |
SCHED [n] EVENT_04 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #5 |
SCHED [n] EVENT_05 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #6 |
SCHED [n] EVENT_06 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #7 |
SCHED [n] EVENT_07 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #8 |
SCHED [n] EVENT_08 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #9 |
SCHED [n] EVENT_09 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #10 |
SCHED [n] EVENT_10 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #11 |
SCHED [n] EVENT_11 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #12 |
SCHED [n] EVENT_12 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #13 |
SCHED [n] EVENT_13 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #14 |
SCHED [n] EVENT_14 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #15 |
SCHED [n] EVENT_15 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Event #16 |
SCHED [n] EVENT_16 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Status |
SCHED [n] STATUS |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Start Schedule |
SCHED [n] START |
UINT2 |
WO |
UMC800, HC900 |
|
Hold Schedule |
SCHED [n] HOLD |
UINT2 |
WO |
UMC800, HC900 |
|
Advance Schedule |
SCHED [n] ADVANCE |
UINT2 |
WO |
UMC800, HC900 |
|
Reset Schedule |
SCHED [n] RESET |
UINT2 |
WO |
UMC800, HC900 |
|
Time Units |
SCHED [n] UNITS_TIME |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |