Set point scheduler values

Devices supported

The following table lists the devices that support the Set Point Also known as SP. The desired value of a process variable. Setpoint (SP) is an analog point parameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. Scheduler A facility used to schedule the control of a point on either a periodic or once only (demand) basis. See also: demand scan, periodic scan, point. Values, and their formats.

Device Supported Address Format Range

UMC800

SCHED [n] [param]

[n] = 1 to 1

HC900 Hybrid controller.

SCHED [n] [param]

[n] = 1 to 2

Parameters

The following table lists the details of the Scheduler Values parameters.

Param Address Line Param Format Access Devices

Output #1

SCHED [n] OUTPUT11

Floating Point

RO

UMC800, HC900

Output #1

SCHED [n] OUTPUT2

Floating Point

RO

UMC800, HC900

Output #1

SCHED [n] OUTPUT3

Floating Point

RO

UMC800, HC900

Output #4

SCHED [n] OUTPUT4

Floating Point

RO

UMC800, HC900

Output #5

SCHED [n] OUTPUT5

Floating Point

RO

UMC800, HC900

Output #6

SCHED [n] OUTPUT6

Floating Point

RO

UMC800, HC900

Output #7

SCHED [n] OUTPUT7

Floating Point

RO

UMC800, HC900

Output #8

SCHED [n] OUTPUT8

Floating Point

RO

UMC800, HC900

Auxiliary Output #1

SCHED [n] AUX_OUT1

Floating Point

RO

UMC800, HC900

Auxiliary Output #2

SCHED [n] AUX_OUT2

Floating Point

RO

UMC800, HC900

Auxiliary Output #3

SCHED [n] AUX_OUT3

Floating Point

RO

UMC800, HC900

Auxiliary Output #4

SCHED [n] AUX_OUT4

Floating Point

RO

UMC800, HC900

Auxiliary Output #5

SCHED [n] AUX_OUT5

Floating Point

RO

UMC800, HC900

Auxiliary Output #6

SCHED [n] AUX_OUT6

Floating Point

RO

UMC800, HC900

Auxiliary Output #7

SCHED [n] AUX_OUT7

Floating Point

RO

UMC800, HC900

Auxiliary Output #8

SCHED [n] AUX_OUT8

Floating Point

RO

UMC800, HC900

Current Program Number

SCHED [n] PROG_NO

Floating Point

RW

UMC800, HC900

Current Segment Number

SCHED [n] SEG_NO

Floating Point

RW

UMC800, HC900

Program Elapsed Time

SCHED [n] EL_TIME

Floating Point

RO

UMC800, HC900

Segment Time Remaining

SCHED [n] TIME_REMAIN

Floating Point

RO

UMC800, HC900

Schedule Save Request

SCHED [n] SCHED_SAVE

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #1

SCHED [n] SOAK_LIMIT_1

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #2

SCHED [n] SOAK_LIMIT_2

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #3

SCHED [n] SOAK_LIMIT_3

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #4

SCHED [n] SOAK_LIMIT_4

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #5

SCHED [n] SOAK_LIMIT_5

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #6

SCHED [n] SOAK_LIMIT_6

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #7

SCHED [n] SOAK_LIMIT_7

Floating Point

RW

UMC800, HC900

Guaranteed Soak Limit #8

SCHED [n] SOAK_LIMIT_8

Floating Point

RW

UMC800, HC900

Jog Segment

SCHED [n] JOG_SEG

Floating Point

RW

UMC800, HC900

Event #1

SCHED [n] EVENT_01

Discrete (bits).

[Status Point A type of standard point that is used to represent discrete or digital field values. See also: dual-bit status point, standard point. Only]

RO

UMC800, HC900

Event #2

SCHED [n] EVENT_02

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #3

SCHED [n] EVENT_03

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #4

SCHED [n] EVENT_04

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #5

SCHED [n] EVENT_05

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #6

SCHED [n] EVENT_06

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #7

SCHED [n] EVENT_07

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #8

SCHED [n] EVENT_08

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #9

SCHED [n] EVENT_09

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #10

SCHED [n] EVENT_10

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #11

SCHED [n] EVENT_11

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #12

SCHED [n] EVENT_12

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #13

SCHED [n] EVENT_13

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #14

SCHED [n] EVENT_14

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #15

SCHED [n] EVENT_15

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Event #16

SCHED [n] EVENT_16

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Status

SCHED [n] STATUS

Discrete (bits).

[Status Point Only]

RO

UMC800, HC900

Start Schedule

SCHED [n] START

UINT2

WO

UMC800, HC900

Hold Schedule

SCHED [n] HOLD

UINT2

WO

UMC800, HC900

Advance Schedule

SCHED [n] ADVANCE

UINT2

WO

UMC800, HC900

Reset Schedule

SCHED [n] RESET

UINT2

WO

UMC800, HC900

Time Units

SCHED [n] UNITS_TIME

Discrete (bits).

[Status Point Only]

RW

UMC800, HC900