Set point programmer #4 profile segment
Devices supported
The following table lists the devices that support the Set Point Also known as SP. The desired value of a process variable. Setpoint (SP) is an analog point parameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. Programmer #4 Profile Segment, and their formats.
| Device | Supported Address Format | Range |
|---|---|---|
|
DR4300 |
SPP4_SEG [n] [param] |
[n] = 1 to 24 |
|
DR4500 |
SPP4_SEG [n] [param] |
[n] = 1 to 12 |
|
UDC2300 |
SPP4_SEG [n] [param] |
[n] = 1 to 12 |
|
UDC3300 |
SPP4_SEG [n] [param] |
[n] = 1 to 12 |
|
UMC800, HC900 Hybrid controller. |
SPP4_SEG [n] [param] |
[n] = 1 to 50 |
Parameters
The following table lists the details of the Set Point Program #4 Profile Segment parameters.
| Param | Address Line | Param Format | Access | Devices |
|---|---|---|---|---|
|
Ramp/Soak Segment |
SPP4_SEG [n] SEG_TYPE 0 = Soak Segment 1 = Ramp Segment |
Discrete (bits). |
RW |
UMC800, HC900 |
|
Event #1 |
SPP4_SEG [n] EV01 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #2 |
SPP4_SEG [n] EV02 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #3 |
SPP4_SEG [n] EV03 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #4 |
SPP4_SEG [n] EV04 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #5 |
SPP4_SEG [n] EV05 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #6 |
SPP4_SEG [n] EV06 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #7 |
SPP4_SEG [n] EV07 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #8 |
SPP4_SEG [n] EV08 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #9 |
SPP4_SEG [n] EV09 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #10 |
SPP4_SEG [n] EV10 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #11 |
SPP4_SEG [n] EV11 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #12 |
SPP4_SEG [n] EV12 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #13 |
SPP4_SEG [n] EV13 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #14 |
SPP4_SEG [n] EV14 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #15 |
SPP4_SEG [n] EV15 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Event #16 |
SPP4_SEG [n] EV16 |
Discrete (bits). [Status Point Only] |
RW |
UMC800, HC900 |
|
Soak Value for Auxiliary Output |
SPP4_SEG [n] AUX_OUT |
Floating Point |
RW |
UMC800, HC900 |
|
Time |
SPP4_SEG [n] TIME1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Rate |
SPP4_SEG [n] RATE |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Ramp or Soak Value |
SPP4_SEG [n] SEG_VALUE |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |