Set point programmer
Devices supported
The following table lists the devices that support the set point Also known as SP. The desired value of a process variable. Setpoint (SP) is an analog point parameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. programmer, and their formats.
| Device | Supported Address Format | Range |
|---|---|---|
|
DR4300 |
SPP Setpoint in percent. See also: setpoint parameter. [n] [param] |
[n] = 1 to 1 |
|
DR4500 |
SPP [n] [param] |
[n] = 1 to 2 |
|
UDC2300 |
SPP [n] [param] |
[n] = 1 to 1 |
|
UDC3300 |
SPP [n] [param] |
[n] = 1 to 1 |
|
UMC800 |
SPP [n] [param] |
[n] = 1 to 4 |
|
SPP [n] [param] |
[n] = 1 to 4 |
Parameters
The following table lists the details of the set point program parameters.
| Param | Address Line | Param Format | Access | Devices |
|---|---|---|---|---|
|
Set Point Programmer Output |
SPP [n] OUT1 |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Segment Time Remaining |
SPP [n] SEG_TIME_REM |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Start |
SPP [n] START |
UINT2 |
WO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Hold |
SPP [n] HOLD |
UINT2 |
WO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Advance |
SPP [n] ADV |
UINT2 |
WO |
UMC800, HC900 |
|
Set Point Programmer Reset |
SPP [n] RESET |
UINT2 |
WO |
UMC800, HC900 |
|
Set Point Programmer Status - Ready |
SPP [n] STATUS_READY |
Discrete (bits). |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - Run |
SPP [n] STATUS_RUN |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - Hold |
SPP [n] STATUS_HOLD |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - End |
SPP [n] STATUS_END |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - Time Units in Seconds |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
|
Set Point Programmer Status - Time Units in Minutes |
SPP [n] STATUS_TIME_UNIT_M |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - Time Units in Hours |
SPP [n] STATUS_TIME_UNIT_H |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Elapsed Time |
SPP [n] EL_TIME |
Floating Point |
RO |
UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Status - Ramp Rate |
SPP [n] STATUS_RAMP_RATE |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300 |
|
Set Point Programmer Status - Ramp Units |
SPP [n] STATUS_RAMP_UNITS |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point Programmer Current Segment Number |
SPP [n] SEG_NO |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300 |
|
Set Point Programmer Current Segment Number |
SPP [n] SEG_NO |
Floating Point |
RW |
UMC800, HC900 |
|
Set Point Programmer Status - Type of Hold |
SPP [n] STATUS_HOLD_TYPE |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Status - Current Segment is a ramp |
SPP [n] STATUS_RAMP |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #1 |
SPP [n] EV01 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #2 |
SPP [n] EV02 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #3 |
SPP [n] EV03 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #4 |
SPP [n] EV04 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #5 |
SPP [n] EV05 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #6 |
SPP [n] EV06 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #7 |
SPP [n] EV07 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #8 |
SPP [n] EV08 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #9 |
SPP [n] EV09 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #10 |
SPP [n] EV10 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #11 |
SPP [n] EV11 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #12 |
SPP [n] EV12 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #13 |
SPP [n] EV13 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #14 |
SPP [n] EV14 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #15 |
SPP [n] EV15 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Set Point Programmer Segment Event #16 |
SPP [n] EV16 |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |