PID loop
Devices supported
The following table lists the devices that support PID Proportional, integral, and derivative control modes. Loops, and their formats.
| Device | Supported Address Format | Range |
|---|---|---|
|
LOOP [n] [param] |
[n] = 1 to 24 |
|
|
HC900 |
LOOPX [n] [param] |
[n] = 25 to 32 |
|
DR4300 |
LOOP [n] [param] |
[n] = 1 to 1 |
|
DR4500 |
LOOP [n] [param] |
[n] = 1 to 2 |
|
UDC2300 |
LOOP [n] [param] |
[n] = 1 to 1 |
|
UDC3300 |
LOOP [n] [param] |
[n] = 1 to 2 |
|
UMC800 |
LOOP [n] [param] |
[n] = 1 to 16 |
Parameters
The following table lists the details of the PID Loop parameters.
| Param | Address Line | Param Format | Access | Devices |
|---|---|---|---|---|
|
Active/Inactive LO |
LOOP [n] STATUS_LO |
Discrete (bits). |
RO |
UMC800, HC900 |
|
Alarm An indication (visual and/or audible) that alerts an operator at a Station of an abnormal or critical condition. Each alarm has a type and a priority. Alarms can be assigned either to individual points or for system-wide conditions, such as a controller communications failure. Alarms can be viewed on a Station display and included in reports. Experion classifies alarms into the following types: - PV Limit - Unreasonable High and Unreasonable Low - Control Failure - External Change. #1 SP The setpoint parameter of an analog point. The desired value of a process variable. Setpoint (SP) is an analog pointparameter, and the value is entered by the operator. The setpoint can be changed any number of times during a single process. The setpoint is represented in engineering units. See SP in the Control Builder Parameter Reference. See also: analog point, parameter, process variable. #1 |
LOOP [n] AL1SP1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Alarm #1 SP #2 |
LOOP [n] AL1SP2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Alarm #2 SP #1 |
LOOP [n] AL2SP1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Alarm #2 SP #2 |
LOOP [n] AL2SP2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
LOOP [n] ANTI_SOOT |
Discrete (bits). [Status Point Only] Bit 0, 0 = Off, 1 = On |
RW |
UMC800, HC900 |
|
|
Auto/Manual |
LOOP [n] AMSTAT |
Discrete (bits). [Status Point Only] |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
BIAS |
LOOP [n] BIAS |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Carbon Potential Dewpoint |
LOOP [n] CPD |
Floating Point |
RW |
UMC800, HC900 |
|
Currently Selected Local or Remote In Honeywell terminology, refers to a device that is not physically connected to the Experion process control network. Set Point |
LOOP [n] STATUS_RSP |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Currently Selected Set Point |
LOOP [n] STATUS_SP |
Discrete (bits). [Status Point Only] |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Currently Selected Tune Set |
LOOP [n] STATUS_TUNE |
Discrete (bits). [Status Point Only] Bit 0, 0 = Tune Set 1, 1 = Tune Set 2 |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Cycle Time #1 |
LOOP [n] CYCLE1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300 |
|
RO |
UMC800, HC900 |
|||
|
Cycle Time #2 |
LOOP [n] CYCLE2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300 |
|
RO |
UMC800, HC900 |
|||
|
DB |
LOOP [n] DB |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Demand Tune Request |
LOOP [n] TUNE_REQ |
Discrete (bits). [Status Point Only] Bit 0, 0 = Off, 1 = On |
RW |
UMC800, HC900 |
|
Deviation |
LOOP [n] DEV |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
DIR |
LOOP [n] DIR |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Feed Forward Gain |
Floating Point |
RW |
UMC800, HC900 |
|
|
Furnace Factor |
LOOP [n] FFCTR |
Floating Point |
RW |
UMC800, HC900 |
|
Fuzzy State |
LOOP [n] FUZZY_STATE |
Discrete (bits). [Status Point Only] Bit 0, 0 = Disable, 1 = Enable |
RW |
UMC800, HC900 |
|
Gain #1 (Prop Band #1 if active) |
LOOP [n] GAIN1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Gain #2 (Prop Band #2 if active) |
LOOP [n] GAIN2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
IMAN Active/Inactive |
LOOP [n] STATUS_IMAN |
Discrete (bits). [Status Point Only] |
RO |
UMC800, HC900 |
|
Input #1 |
LOOP [n] INP1 |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Input #2 |
LOOP [n] INP2 |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300 |
|
Local Percent Carbon Monoxide |
LOOP [n] PCTCO |
Floating Point |
RW |
UMC800, HC900 |
|
Local Set Point #1 |
LOOP [n] LSP1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Local Set Point #2 |
LOOP [n] LSP2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Local Set Point #3 |
LOOP [n] LSP3 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300 |
|
Manual Reset |
LOOP [n] MAN_RESET |
Floating Point |
RW |
UMC800, HC900 |
|
On/Off Output Hysteresis |
LOOP [n] OUT_HYST |
Floating Point |
RW |
UMC800, HC900 |
|
OP High Limit |
LOOP [n] OPHIGH |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Output |
LOOP [n] OP |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Output Low Limit |
LOOP [n] OPLOW |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Output Override Value |
LOOP [n] OPOVR |
Floating Point |
RW |
UDC2300, UDC3300 |
|
Output Working Value |
LOOP [n] OPWORK |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Percent Hydrogen |
LOOP [n] H2 |
Floating Point |
RW |
UMC800, HC900 |
|
LOOP [n] PVHIGH |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
|
PV Low Range |
LOOP [n] PVLOW |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
LOOP [n] PV1 |
Floating Point |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
|
Process Variable Override Value |
LOOP [n] PVOVR |
Floating Point |
RW |
UDC2300, UDC3300 |
|
Prop Band #1 |
LOOP [n] PROP1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Prop Band #2 |
LOOP [n] PROP2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Rate #1 |
LOOP [n] RATE1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
RATIO |
LOOP [n] RATIO |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Read-only AUTO/MAN Mode |
LOOP [n] STATUS_MODE |
Discrete (bits). [Status Point Only] Bit 0, 0 = Man, 1 = Auto |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Read-only mode for the PID Loop |
LOOP [n] LOOPSTAT |
Mode Status - Bit 0 = Auto/Man State. Bit 2 = LSP/RSP State. |
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Remote/Local Set Point State |
LOOP [n] RSP_STATE |
Discrete (bits). [Status Point Only] Bit 0, 0 = LSP, 1 = RSP |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Remote Set Point (RSP) |
LOOP [n] RSP |
Floating Point |
RW |
UMC800, HC900 |
|
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|||
|
Reset #1 |
LOOP [n] RESET1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Reset #2 |
LOOP [n] RESET2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Rate #2 |
LOOP [n] RATE2 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point #1 |
LOOP [n] SP1 |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Set Point #2 |
LOOP [n] SP2 |
Floating Point |
RW |
UMC800, HC900 |
|
RO |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|||
|
Set Point Override Value |
LOOP [n] SPOVR |
Floating Point |
RW |
UDC2300, UDC3300 |
|
Set Point State |
LOOP [n] SP_STATE |
Discrete (bits). [Status Point Only] |
RW |
UDC2300, UDC3300 |
|
Discrete (bits). [Status Point Only] Bit 0, 0 = SP1, 1 = SP2 |
RW |
DR4300, DR4500, UDC2300, UMC800, HC900 |
||
|
SP Low Limit |
LOOP [n] SPLOW |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
SP High Limit |
LOOP [n] SPHIGH |
Floating Point |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Temperature in carbon potential loop |
LOOP [n] TEMP |
Floating Point |
RO |
UMC800, HC900 |
|
Three Position Step Motor Time |
LOOP [n] MOTOR |
Floating Point |
RW |
UMC800, HC900 |
|
Tune Set State |
LOOP [n] TUNE_SET_STATE |
Discrete (bits). [Status Point Only] |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |
|
Working Set Point (SPWORK) |
LOOP [n] WSP |
Floating Point |
RO |
DR4300, DR4500 |
|
RW |
UDC2300, UDC3300, UMC800, HC900 |
|||
|
Working Set Point (WSP) |
LOOP [n] SPWORK |
Floating Point |
RW |
UMC800, HC900 |
|
RO |
DR4300, DR4500, UDC2300, UDC3300 |
|||
|
LOOP [n] MODEIN |
Control Mode - Auto/Man State (bit 0) and LSP/RSP State (bit 2). |
RW |
DR4300, DR4500, UDC2300, UDC3300, UMC800, HC900 |